What it is for
This is the box the market actually buys. A certified 40HC shell, two power cabinets, sixteen negative-pressure fans, and a cold aisle wide enough that a technician can pull a machine without dismantling its neighbour.
It is rated at 180 kW because that is where air still works: above that the fans stop earning their keep and the exhaust temperature climbs faster than the airflow does. If you need more per box, water cooling is the next step, not a bigger fan.
Where it is typically used
Key specifications
| Shell | 40HC, CSC plated, 12,192 × 2,438 × 2,896 mm |
| Machines | 336 at 5.7 kW class, 4 columns × 84 |
| Design load | 180 kW at 35 °C ambient |
| Power | 2 cabinets, 1,200 A main, 1 breaker per position |
| PDU | 28 strips, 12 × C19 + 1 × C13, switchable per socket |
| Airflow | 16 × 1,220 mm negative-pressure fans, 0.75 kW each |
| Inlet | 100 mm aluminium water curtain + 40-mesh filter |
| Network | 16 × 24-port switches + 1 aggregation, labelled and tested |
| Weight | About 24 t loaded, 4 corner castings for lifting |
| Build time | 30–45 days from drawing release |
Figures are for the standard configuration and change with the project. Values are design values; acceptance follows the contract technical agreement.
What goes in the box
Installed, wired and tested before dispatch. On site the work is placement and external connections.
CSC plate, 50 mm insulated roof, service and escape doors at both ends.
Main breaker, branch protection per position, UL/CSA or IEC cable to destination.
Switchable per socket, mounted at standing height rather than at floor level.
Negative-pressure fans, curtain or snow baffle, cold and hot aisle separation panels.
Switches, one cable per machine, plus belts, a fan motor and a PDU strip in the box.
Which model to take
| Model | Machines | Load | Inlet | Ambient |
|---|---|---|---|---|
| MC-AIR-40-S | 336 | 180 kW | Water curtain | 35 °C |
| MC-AIR-40-H | 336 | 180 kW | Curtain + pre-cool | 42 °C |
| MC-AIR-40-C | 300 | 165 kW | Snow baffle | −25 °C |
Standard models are listed. Other capacities are built to order, with two to three weeks added to the standard lead time.
Why the fans pull instead of push
Negative pressure puts the dust where you can reach it
A pressurised box leaks hot air out of every seam, and the dust comes in wherever the pressure is lowest — usually around the cable entries, on top of the boards. A negative-pressure box pulls air through one filtered inlet, so what you clean is a curtain and a mesh panel, not 336 heat sinks.
The cost is fan power and about 100 mm of usable width. At 180 kW that trade is worth taking; at 1.2 MW the fans cannot move enough air at all, which is why the water-cooled box exists.
When to use it, when not to
These come from projects rather than general advice. Match your case against them; it is more useful than reading the specification table.
This is the configuration the design was drawn around.
Nothing is cast in; the shell retains its CSC plate and its resale value.
The fans will not keep up and the machines will throttle. Take the water-cooled 40HC.
A dirty inlet turns 180 kW into 140 kW within a season. Be honest about the maintenance.
From contract to energisation
Machine model, wattage, ambient, voltage and inlet choice. Five days to a drawing.
30–45 days, with the electrical build photographed stage by stage.
Four hours at rated load on a resistive bank, ambient logged.
One 40HC per box, loaded with the spares kit and the test sheet inside.
On site and in detail




Some images are scheme illustrations and renders showing structure and layout. Final delivery follows the contract drawings.
What customers ask most
Is 336 machines an S19 or an S21 count?
Both fit if the wattage per position matches. The count is set by the power, not by the model name — send the model and we size to it.
Can the water curtain be deleted?
Yes. A snow baffle replaces it in cold climates, or an air hood in dusty ones. Both change the airflow calculation, so they are options rather than deletions.
How loud is it?
68–72 dB(A) at ten metres. Plan the fence line and the prevailing wind before the layout.
What is in the spares kit?
One fan motor, thirty belts, one PDU strip, a set of sockets, a motor protection relay and breakers.
Ask for a scheme for your site
Send the capacity, rack count, site conditions and local climate. You get a layout, a single-line diagram and a price, at no charge, revised until it works.