IT Module (Rack Module)

IT Module (Rack Module)

Racks, cold aisle and cable management only: connect a busbar and a chilled-water pipe and it is a data hall.

4–9racks
250–500kW
8–60kW per rack
IP54enclosure
01 / OVERVIEW

What it is for

The IT module is the building block of the range. It handles racks, the cold aisle, cable management and sprinkler heads. Power comes from outside and cooling comes from outside.

It is designed that way to work with infrastructure the customer already has. If there is a switch room, a chiller plant and generators, and the only thing missing is floor space, buy the IT module and bring power and water to it.

It also runs the other way: buy the IT module now to get the service live, and add the power and cooling modules next year. The real value of modularity is not speed, it is being able to buy in stages.

Three lengths. 10 ft takes two racks for a small branch, 20 ft takes four, 40 ft takes seven to nine. Rack count follows aisle width rather than floor area: two rows need at least 1.2 m between them or a loaded trolley will not pass.

Where it is typically used

Power and cooling already available, floor space missingThe cheapest route: buy the enclosure only and bring services in.
Phased delivery, service firstRun on temporary power initially, then connect the permanent power and cooling modules in phase two.
Liquid cooling retrofit, existing enclosure too smallCold plates and manifolds need space that a standard enclosure cannot give, so move to a high-density IT module.
02 / SPECIFICATIONS

Key specifications

Length 10 ft (3.0 m) / 20 ft (5.9 m) / 40 ft (12.03 m)
Racks 2 / 4 / 7–9 at 600 × 1200 × 2000 mm
Power per rack 8–25 kW air-cooled / 30–60 kW liquid-cooled
Total IT load 80 kW / 150 kW / 250–500 kW
Cooling interface Chilled water DN50 flow and return, or duct connection
Air distribution Underfloor supply with sealed cold aisle; in-row cooling optional
Power interface Busbar 400/630 A, or cable entry
Fire Sprinkler and detection interfaces, routed to an external cylinder bank
Enclosure 1.5–2.0 mm corrugated steel with 100 mm rock wool, IP54
Floor 8 kN/m² standard, 12 kN/m² in the rack zone
Seismic To site requirements, up to intensity 8

Figures are for the standard configuration and change with the project. Values are design values; acceptance follows the contract technical agreement.

03 / WHAT IS INSIDE

What goes in the box

Installed, wired and tested before dispatch. On site the work is placement and external connections.

01Structure

Corrugated steel skin, rock wool core, damp-proof layer, steel base frame, lifting lugs at the corners.

02Racks

42U or 47U, 78% open front door, double rear doors, brush entry at the top.

03Cold aisle

Frame, clear roof panels, end doors, and a full blanking panel kit.

04Floor and grilles

600 × 600 calcium sulphate tiles, grilles at 25/40/60% open area by load.

05Cable management

Separate power and data trays overhead, dedicated fibre tray, continuous earth bar.

06Fire interfaces

Sprinkler heads, detection, pressure relief, sounder beacons, terminal blocks ready.

07Liquid-ready

Manifold position, quick couplings and leak detection rope as an option.

04 / MODELS

Which model to take

Model Length Racks IT load Cooling Notes
AIDC-IT10 10 ft 2 80 kW Air Small branch
AIDC-IT20 20 ft 4 150 kW Air Standard
AIDC-IT40 40 ft 7 250 kW Air Workhorse
AIDC-IT40H 40 ft 9 500 kW Liquid High density

Standard models are listed. Other capacities are built to order, with two to three weeks added to the standard lead time.

05 / TECHNICAL NOTES

How to size power per rack, and when air cooling runs out

ENGINEERING NOTE

Separate kW from kVA first

Rack nameplates often state kVA while the heat is in kW. The difference is power factor, typically above 0.95 on modern server supplies and around 0.9 on older equipment.

A rack rated 20 kVA at 0.95 power factor draws at most 19 kW. Size cooling against 20 kW and you are marginally short; size the UPS against 20 kVA and you are right. The two numbers are not interchangeable.

There is an easier mistake: nameplate power is supply capacity, not consumption. A 2U server with an 800 W supply may draw 350 W. Sizing on the nameplate grossly oversizes; sizing on measurements is unsafe. The industry convention is to estimate at 70%–80% of nameplate.

Where air cooling stops

Air carries heat away, and how much depends on volume and temperature difference. A 42U rack with 12 °C across it and 3000 m³/h of airflow theoretically removes about 12 kW. To reach 25 kW the airflow has to double, and noise and fan power rise with it.

In practice the comfortable band for air is 8–15 kW per rack, stretched to 25 kW with effort, and beyond that it becomes a struggle: deeper racks, bigger fans, higher static pressure, and underfloor supply stops coping.

Thirty kilowatts is the accepted ceiling for air. Above that it is liquid cooling or a hybrid.

Liquid cooling is not one thing

Cold plate: a metal plate sits on the CPU or GPU, coolant runs through it and removes 70%–80% of the heat, while memory, drives and PSUs still rely on air. Retrofit costs are low, which is why it dominates today.

Immersion: the whole server sits in dielectric fluid and 100% of the heat leaves through the liquid. The most thorough thermal solution, but servers need modification to remove fans, maintenance is awkward and the fluid is expensive.

Spray: coolant is sprayed directly onto components, sitting between the two, with a few vendors shipping it and few reference sites so far.

Above 60 kW per rack, cold plate is effectively the only realistic option. Something like a GB200 NVL72 at 120 kW per rack has no air path at all.

The one-line version

Under 15 kW per rack: air, with a sealed cold aisle, is enough.

15–30 kW: enhanced air (in-row units plus containment), or liquid-ready cold plate.

Above 30 kW: cold plate liquid, without hesitation.

At that point the questions are no longer only thermal. They are distribution (busway or cable), structure (1.5 t per rack) and fire (whether the coolant is flammable).

Estimate the real load at nameplate times 0.75 and leave 20% headroom. Sizing at full nameplate wastes half the cooling capacity; sizing on measurements fails in the hottest week of summer.

06 / SELECTION

When to use it, when not to

These come from projects rather than general advice. Match your case against them; it is more useful than reading the specification table.

Switch room and cooling plant exist, floor space missing

Buy the IT module only and bring power and water in. Cheapest option available.

No external cooling source

The IT module has no cooling of its own. Add a cooling module, or specify in-row units.

Staged purchase: service now, power next year

Run on temporary power first, then connect the permanent power module in phase two.

Over 60 kW per rack and no appetite for liquid

Air cannot do it and no manufacturer can. Do not be talked into it.

07 / DELIVERY

From contract to energisation

Confirmation · 3 days

Length, rack count, power per rack, air or liquid-ready.

Drawings · 1 week

Layout, rack arrangement, interface positions, load points.

Production · 3–4 weeks

Enclosure, insulation, floor, racks, trays, fire pipework.

FAT · 1 day

Dimensional check, earth resistance, fire pipe pressure test.

Site · 2–3 days

Placement, busbar and water connection, server installation.

08 / GALLERY

On site and in detail

A fitted IT module with in-row cooling set into the rack row
A fitted IT module with in-row cooling set into the rack row
Empty enclosure: floor, trays and fire pipework in place
Empty enclosure: floor, trays and fire pipework in place
Contained cold aisle and perforated floor
Contained cold aisle and perforated floor
Two rack rows facing each other
Two rack rows facing each other

Some images are scheme illustrations and renders showing structure and layout. Final delivery follows the contract drawings.

09 / FAQ

What customers ask most

Can I supply my own racks?

Yes. We deliver an empty enclosure, but rack dimensions and fixing centres must be given in advance and the floor cut-outs aligned.

How much does liquid-ready add?

Cold-plate preparation (manifold position, quick couplings, leak detection) adds roughly 8%–12%. The full liquid system of CDU, pipework and cold plates is separate and usually comes with the server vendor.

Can a UPS go inside?

Yes, but it takes 1–1.5 rack positions and its heat has to be added to the cooling load. Where space allows, keep it separate.

How many racks fit in 10 ft?

Two, at 600 or 1200 mm deep. At 1200 mm deep the aisle shrinks to 0.9 m and trolleys become awkward.

How long does the enclosure last?

25 years structural, 15 years insulation, 8–10 years for door seals. Coastal sites should add a protective coating and inspect every five years.

Ask for a scheme for your site

Send the capacity, rack count, site conditions and local climate. You get a layout, a single-line diagram and a price, at no charge, revised until it works.

See the full range

Product Details

Capacity in units, not in buildings

A module is a steel-framed, insulated, wired enclosure that holds racks, cooling and distribution and
arrives ready to couple to the next one. Two modules make a hall; four make a small campus. Each one is
tested alone, so a failure stays inside its own shell.

Where modules beat a build

Campus expansions that cannot wait for a construction programme. Sites where the power feed arrives in
stages and the IT has to follow it. Operators who want to add a row of racks without shutting the existing
row down — the new module is commissioned cold and cut over in a window.

Key figures

  • Steel frame, insulated panel envelope · ISO footprint or custom skid
  • Rack, PDU, cooling and containment fitted and tested at the factory
  • Cable, pipe and busway interfaces brought to one face for fast coupling
  • Transport brackets rated for sea freight, not just for a flatbed
  • Lifting points and centre-of-gravity drawing issued with every unit

Built to order. Tell us the rack count and the ambient and we size the module around it.

gallery
RELATED PRODUCT
AIDC cool — main image
Cooling Module
AIDC pair20 — main image
20 ft Twin-Module Data Centre
AIDC campus — main image
Modular Data Centre Campus
Containerised data centre, exterior view (catalogue crop)
40 ft Containerised Data Hall
Contact us

Committed to providing customers with high-quality and reliable container solutions.