20 ft Twin-Module Data Centre

20 ft Twin-Module Data Centre

IT in one 20 ft enclosure and power in the other, so battery risk and switchgear heat stay away from the servers.

6–7racks
250kW IT load
2 × 20ft modules
400kVA UPS
01 / OVERVIEW

What it is for

The problem with a single enclosure is that IT equipment and electrical plant share one space. Heat, dust and electromagnetic interference all mix, the UPS and switchgear generate their own heat, and they occupy floor positions that could hold racks.

The twin module splits the two functions. The IT enclosure holds racks and cooling only; the power enclosure holds UPS, distribution and batteries. A prefabricated cable tray or busbar links them across an adjustable 1.5–3 m.

There are three gains. All the cooling in the IT enclosure goes to racks rather than to switchgear. Batteries are physically separated from IT equipment, so a thermal event stays contained. And the power enclosure can be serviced without stopping the IT enclosure.

The cost is a second enclosure, a second foundation and a link between them, which comes to roughly 12%–18% more than a single enclosure of the same capacity. Maintainability and safety, however, move up a category.

Where it is typically used

Mid-sized corporate data room200–250 kW, needing IT and power physically separated, with no room for two buildings.
Switch room exists, clean space missingTake power from the existing switch room and buy only the IT module, or the reverse and add only a power module.
2N required, budget limitedSplit the boxes and put 2N on the power side with N+1 on IT, spending where it matters.
02 / SPECIFICATIONS

Key specifications

Module configuration 20 ft IT module plus 20 ft power module
Racks 6 standard / 7 compact
Power per rack 10–30 kW
Total IT load 200–250 kW
UPS 400 kVA modular, 15 minutes autonomy
Cooling 2 × 35 kW, N+1, sealed cold aisle
Link Prefabricated tray and busbar, 1.5–3 m
Fire Independent detection in each enclosure, shared cylinder bank
Protection IP54
Footprint About 55 m² including both enclosures and the link

Figures are for the standard configuration and change with the project. Values are design values; acceptance follows the contract technical agreement.

03 / WHAT IS INSIDE

What goes in the box

Installed, wired and tested before dispatch. On site the work is placement and external connections.

01IT module

Six racks, cold aisle, two 35 kW cooling units, sprinkler heads.

02Power module

400 kVA UPS, incoming and outgoing panels, ATS, battery racks.

03Link section

Prefabricated tray or busbar, fire-stopped where it passes through, demountable.

04Fire

Cylinders in the power module, pipework run to the IT module in two zones with independent valves.

05Monitoring

Sensors in both enclosures, one controller.

04 / MODELS

Which model to take

Model IT load Racks UPS Cooling
PAIR20-200 200 kW 6 400 kVA 2 × 30 kW
PAIR20-250 250 kW 6 400 kVA 2 × 35 kW
PAIR20-250H 250 kW 7 400 kVA × 2 2 × 35 kW

Standard models are listed. Other capacities are built to order, with two to three weeks added to the standard lead time.

05 / TECHNICAL NOTES

Where the single point of failure sits in a twin module

ENGINEERING NOTE

Separated, but not completely

Splitting IT and power into two boxes looks like two independent pieces of equipment. In practice they only work connected, and that connection becomes the new single point of failure.

The busbar is the usual culprit: a 1.5 m copper run through a wall between the two enclosures. Unprotected and unredundant, its failure stops the system. The industry answer is either dual busbars or a link section built as a quick-replace plug-in.

Water is the second. If the IT module uses chilled water, the pipe crosses from the cooling or power module. Insulation, waterproofing and frost protection at that penetration are the easiest things on site to get wrong.

Communication is the third. The two monitoring controllers talk over one cable, and if it breaks the alarms stop leaving the site. Use a wireless backup or dual routing.

Why it is still worth doing

Because it moves the biggest risk out of the way. Battery thermal runaway is one of the most dangerous failures in a data centre: a lithium fire reaches over 800 °C and is hard to extinguish. With the battery in another enclosure behind a fire wall, at minimum it is not burning the servers directly.

Then there is maintenance. Annual UPS service involves a transfer, and with the UPS in the same box as the IT, people and tools move past the racks and things get unplugged. Separated, that problem disappears.

And capacity. Leave 20% headroom in the power module and racks can be added later without replacing electrical plant; conversely the power module can be upsized without touching the IT module.

When a twin module is the wrong answer

Below 150 kW. The fixed cost of two enclosures, two foundations, the link and the fire system cannot be spread, and a single enclosure is cheaper.

When the site is very tight. A twin module with its link needs 55 m²; a single enclosure needs 30 m².

And if the customer already has a standalone switch room, they should buy only the IT module and take power from the switch room. That is the cheapest option and one we recommend routinely.

Design the link between the enclosures to be replaceable, not welded. Once it is welded, moving or replacing either enclosure means stopping the whole system.

06 / SELECTION

When to use it, when not to

These come from projects rather than general advice. Match your case against them; it is more useful than reading the specification table.

150–300 kW, 55 m² of site available

A twin module has the best overall value here, and both safety and maintainability move up a level.

Under 150 kW

The fixed cost does not amortise. Use a single enclosure or the AIDC-40.

Customer already has a standalone switch room

Buy the IT module only and take power from the switch room. Cheapest route.

Site extremely tight, space for one position only

Take the AIDC-40 and accept IT sharing a box with power.

07 / DELIVERY

From contract to energisation

Confirmation · 3 days

Capacity, rack count, link length, dual path or not.

Design · 1 week

Layout of both enclosures, link section, foundation drawings.

Production · 4–5 weeks

Both enclosures built in parallel and integrated before dispatch.

FAT · 2 days

The two enclosures run connected at full load, transfer tested.

Site · 3–5 days

Placement, connection, fire stopping, energisation.

08 / GALLERY

On site and in detail

IT and power enclosures side by side with the cable tray link above
IT and power enclosures side by side with the cable tray link above
Inside the power module: UPS, distribution, ATS
Inside the power module: UPS, distribution, ATS
Battery racks and fire cylinders, physically apart from the IT zone
Battery racks and fire cylinders, physically apart from the IT zone
Rack rows and cold aisle inside the IT module
Rack rows and cold aisle inside the IT module

Some images are scheme illustrations and renders showing structure and layout. Final delivery follows the contract drawings.

09 / FAQ

What customers ask most

Do the two enclosures have to be side by side?

No. They can be arranged in an L, or separated by a wall. The link can run to 5 m; beyond that it becomes cable or busway and the price changes.

Can one enclosure be IT and the other cooling?

Yes, sold as an IT plus cooling pair, which suits sites with no chilled-water source. The cooling module needs its own footprint and is noisy, so keep it away from housing.

Are batteries safe in the power enclosure?

Safer than in the IT enclosure, but a separate battery enclosure is better still. Above 200 kWh we recommend three enclosures: IT, power and battery.

Does the link need fire stopping?

Yes. Seal the penetration with intumescent compound or board rated at least as long as the enclosure itself. Acceptance will check it.

Can the two be shipped separately?

Yes. Both are standard 20 ft units on a normal flatbed, no abnormal-load permit needed.

Ask for a scheme for your site

Send the capacity, rack count, site conditions and local climate. You get a layout, a single-line diagram and a price, at no charge, revised until it works.

See the full range

Product Details
gallery
RELATED PRODUCT
AIDC gen — main image
Generator Module
AIDC cool — main image
Cooling Module
AIDC cluster — main image
Prefabricated Data Centre Cluster
Edge data centre container on a concrete pad (catalogue crop)
20 ft Edge Data Centre
Contact us

Committed to providing customers with high-quality and reliable container solutions.