A 20 ft edge data centre container installed beside a telecom mast in open country

Project case · Edge data centre · Client confidential

Twelve edge sites, one container each

A content delivery network needed capacity inside twelve secondary towns — places where a leased suite costs four times the national average, starts at 500 m² and takes nine months to commission. We stopped leasing rooms and started shipping them.

12sites
20 ftfootprint
38days per site
0.9 MWtotal IT load
ClientEdge network operator (confidential)
LocationNorthern Europe, 12 towns
Scope12 × 20 ft edge halls with power and cooling
ContractFrame agreement, DDP, called off per site
HandoverRolling, 2025–2026
01 / The brief

The suites were the wrong size, in the wrong towns, at the wrong price

What the client was up against

Latency budgets are set by distance and the operator’s traffic had moved out of the capitals. In the twelve towns where the caches were needed, commercially available colocation started at half a hall, was priced against a capital-city index, and queued behind other tenants for power and access.

The alternative on the table was a purpose-built edge building per town. Twelve sites at roughly nine months each, twelve planning applications, twelve sets of groundworks, and a capital line the board would not sign in one year.

What we proposed

A single 20 ft pod per town: eight racks, 60 kW of UPS, split DX cooling and a fire panel, all inside one ISO frame that lands on a pad and takes a cable trench, a fibre duct and a meter. Site works reduce to a level pad, a power connection and a duct — the kind of work a local contractor can finish in two weeks.

Because the pod is a product, the twelfth site costs what the first one did and commissions the same way. That is the point of the frame agreement: the design is frozen once, and each call-off is a shipping date rather than a project.

02 / What we delivered

Three systems in a 20 ft footprint

20 ft edge pod
01 / IT hall20 ft edge pod

Eight 600 × 1,200 racks at 6 kW each, one row, cold aisle closed with roof panels and blanking. Cabling overhead in a single ladder, A and B separated.

60 kW UPS, 2N on the IT path
02 / Power60 kW UPS, 2N on the IT path

Two 30 kW modular UPS frames sharing the load, static transfer at the output, and metering per rack position. Generator provision kept outside the pod as a site option.

Split DX with free cooling
03 / CoolingSplit DX with free cooling

Two independent DX circuits, one running, one on standby, with an economiser coil for the 5,500 hours a year this latitude sits below 18 °C.

03 / Sequence

Thirty-eight days from call-off to live — on every one of the twelve

D0Call-offSite survey pack issued; pad and duct positions agreed with the local contractor.
D7Configuration freezeRack count, power rating and fibre entry signed off; build slot booked.
D20Factory testFull-load run at 35 °C ambient, witnessed remotely and recorded.
D30LandingPod delivered on a flatbed, set on the pad, earthed and sealed the same day.
D38LiveFibre spliced, meter closed, remote hands on site, first cache node online.
04 / By the numbers

What twelve call-offs actually delivered

12sites live inside one programme year
0.9 MWtotal IT load, 60 kW per pod
38days average from call-off to first cache node
8racks per pod, 2N on the UPS path

Averages across the twelve sites. Two sites ran longer because the local utility required a new transformer; the pod was on site and idle for 26 and 41 days respectively. Values rounded for confidentiality.

05 / Site record

Site record — pads, pods and the rooms inside them

A twin pod site at the edge of a town: two halls, one shared pad
A twin pod site at the edge of a town: two halls, one shared pad
Single pod with the mast it serves; fibre and power enter from the rear
Single pod with the mast it serves; fibre and power enter from the rear
Cold aisle before racks: containment roof and blanking in place
Cold aisle before racks: containment roof and blanking in place
Louvred wall from outside: condenser intake and service door
Louvred wall from outside: condenser intake and service door
Figures & disclosure

Published as an anonymised reference. The client is not named and the site location is given only to region level. Commercial values (contract sum, unit price) are withheld; the technical figures describe the configuration as delivered. Where a number has been rounded or scaled for confidentiality it is stated in the note above.